Specifications
| Range | TeSys Deca |
|---|---|
| Product name | TeSys GV2 |
| Product or Component Type | Motor circuit breaker |
| Device short name | GV2ME |
| Device Application | Motor protection |
| Trip unit technology | Thermal-magnetic |
| Poles description | 3P |
|---|---|
| Network type | AC |
| Utilisation category | Category A IEC 60947-2 AC-3 IEC 60947-4-1 AC-3e IEC 60947-4-1 |
| Network frequency | 50/60 Hz IEC 60947-2 |
| Motor power kW | 2.2 kW 400/415 V AC 50/60 Hz 3 kW 500 V AC 50/60 Hz 4 kW 690 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 50 kA Icu 500 V AC 50/60 Hz IEC 60947-2 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 75 % 690 V AC 50/60 Hz IEC 60947-2 |
| Control Type | Push-button |
| Line Rated Current | 6.3 A |
| Thermal protection adjustment range | 4…6.3 A IEC 60947-2 |
| Magnetic tripping current | 91 A |
| [Ith] conventional free air thermal current | 6.3 A IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV IEC 60947-2 |
| Phase failure sensitivity | Yes IEC 60947-4-1 |
| Suitability for isolation | Yes IEC 60947-1 |
| Power dissipation per pole | 2.5 W |
| Mechanical durability | 100000 cycles |
| Electrical durability | 100000 cycles AC-3 415 V In 100000 cycles AC-3e 415 V In |
| Rated duty | Uninterrupted IEC 60947-4-1 |
| Connections – terminals | Power circuit: screw clamp terminal 2 cable(s) 0.002…0.009 in² (1…6 mm²) – solid Power circuit: screw clamp terminal 2 cable(s) 0.002…0.009 in² (1.5…6 mm²) – flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 0.002…0.006 in² (1…4 mm²) – flexible with cable end |
| Tightening torque | 15.05 lbf.in (1.7 N.m) screw clamp terminal |
| Fixing mode | 35 mm symmetrical DIN rail clipped Panel screwed with adaptor plate) |
| Mounting position | Horizontal Vertical |
| Width | 1.8 in (45 mm) |
| Height | 3.5 in (89 mm) |
| Depth | 3.09 in (78.5 mm) |
| Net Weight | 0.57 lb(US) (0.26 kg) |