[Input]:
| AC operation | |
| Nominal input voltage range | 100 V AC … 240 V AC -15 % / +10 % |
| Input voltage range | 85 V AC … 264 V AC |
| Derating IStat. Boost | < 100 V AC (1 %/V) |
| Input voltage range DC | 110 V DC … 350 V DC (typ. 90 V DC (UL 508: ≤ 300 V DC)) |
| Electric strength, max. | 300 V AC |
| Typical national grid voltage | 120 V AC |
| 230 V AC | |
| Voltage type of supply voltage | AC |
| Inrush current | < 15 A |
| Inrush current integral (I2t) | < 1.5 A2s |
| Inrush current limitation | 15 A |
| AC frequency range | 45 Hz … 65 Hz |
| Frequency range DC | 0 Hz |
| Mains buffering time | > 36 ms (120 V AC) |
| > 36 ms (230 V AC) | |
| Current consumption | 4 A (100 V AC) |
| 1.7 A (240 V AC) | |
| Nominal power consumption | 302 VA |
| Protective circuit | Transient surge protection; Varistor, gas-filled surge arrester |
| Power factor (cos phi) | 0.85 |
| Typical response time | < 0.15 s |
| Input fuse | 10 A (slow-blow, internal) |
| Permissible backup fuse | B10 B16 AC: |
| Permissible DC backup fuse | DC: Connect a suitable fuse upstream |
| Recommended breaker for input protection | 10 A … 20 A (Characteristics B, C, D, K) |
| Discharge current to PE | < 3.5 mA |
| DC operation | |
| Nominal input voltage range | 110 V DC … 250 V DC -10 % … +40 % (UL 508: ≤ 300 V DC) |
| Input voltage range | 110 V DC … 350 V DC |
| Derating IStat. Boost | < 110 V DC (1 %/V) |
| Current consumption | 3.4 A (110 V DC) |
| 1.5 A (250 V DC) | |
[Output]:
| Efficiency | typ. 92 % (120 V AC) |
| typ. 93.2 % (230 V AC) | |
| Output characteristic | U/I |
| Nominal output voltage | 24 V DC ±1 % |
| Setting range of the output voltage (USet) | 18 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted) |
| Nominal output current (IN) | 10 A |
| POWER BOOST (IBoost) | 15 A (-25 °C … 40 °C permanent, UOUT = 24 V DC ) |
| Static Boost (IStat.Boost) | 15 A |
| Selective Fuse Breaking (ISFB) | 60 A (12 ms) |
| Magnetic circuit breaker tripping | B2 / B4 / B6 / C2 / C4 |
| Derating | 60 °C … 70 °C (2.5 %/K) |
| Feedback voltage resistance | ≤ 35 V DC |
| Protection against overvoltage at the output (OVP) | ≤ 35 V DC |
| Control deviation | < 1 % (change in load, static 10 % … 90 %) |
| < 2 % (change in load, dynamic 10 % … 90 %) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | < 50 mVPP (with nominal values) |
| Short-circuit-proof | yes |
| Output power | 240 W |
| 360 W | |
| Maximum no-load power dissipation | 9.1 W |
| Power loss nominal load max. | 22 W |
| Rise time | < 0.05 s (UOUT (10 % … 90 %)) |
| Connection in parallel | yes, for redundancy and increased capacity |
| Connection in series | yes |
| Signal: DC OK active | |
| Output description | UOUT > 0.9 x UN: High signal |
| Switching voltage range | 18 V DC … 24 V DC |
| Maximum inrush current | ≤ 20 mA (short-circuit-proof) |
| Continuous load current | ≤ 20 mA |
| Signal: DC OK floating | |
| Output description | Relay contact, UOUT > 0.9 x UN: Contact closed |
| Maximum switching voltage | 30 V AC |
| 24 V DC | |
| Maximum inrush current | 0.5 A |
| 1 A | |
| Continuous load current | ≤ 1 A |
| Signal: POWER BOOST, active | |
| Output description | IOUT < IN: High signal |
| Switching voltage range | 18 V DC … 24 V DC |
| Output voltage | + 24 V DC |
| Maximum inrush current | 20 mA (short-circuit-proof) |
| Continuous load current | ≤ 20 mA |