[Technical Specification]
Operating Range: 33ft to 262ft, (10 to 80 metres)
Operating Voltage Range: 12 to 36V DC ±10%
Operating Controller Current (with 1 or 2 Receivers): 14mA (constant)
Operating Transmitter Current: 8mA (per Transmitter)
Power Down Reset Time: >20 seconds
Fire and Fault Relay Contacts: VFCO 2A @ 30 Volts DC resistive
Operating Temp. (non-condensing): -10°C to +55°C, (14°f to131°f)
Optical Wavelength: 850nm
LED Indications:
Control Unit –
Red = Fire
Amber = Fault
Green = System OK
Receiver – Alignment LEDs for single person alignment.
IP Rating: IP54 (Controller) / IP66 (Transmitter/Receiver)
Relative Humidity (noncondensing): 93%
Parts List (System):
1 x Transmitter (clear lens)
1 x Receiver (dark lens)
1 x Control Unit
1 x Fixing Kit
2 x Brackets
Parts List (Additional Detector):
1 x Transmitter (clear lens)
1 x Receiver (dark lens)
1 x Fixing Kit
2 x Brackets
Housing Material
(Controller): UL94 V2 PC
(Transmitter/Receiver): Copper Free Aluminum Alloy LM25, red
Cable Gland Entries: 3 x 20mm
ATEX Approval: SIRA 15ATEX1260
[Weight]
Control Unit: 21.37602oz (606g)
Transmitter & Receiver (Inc. Brackets): 8lb 2.513670oz (3.7kg)