Specifications
| Range of product | MasterPact NW Compact NS630…1600 |
|---|---|
| Product name | BA |
| Device short name | BA |
| Product or component type | Automatic controller |
| Range compatibility | MasterPact NT MasterPact NW ComPacT NS630b…1600 Compact NS < 630A MasterPact MTZ |
| [Us] rated supply voltage | 220…240 V AC at 50/60 Hz |
|---|---|
| Mounting location | External |
| Operating mode | Stop (both normal and replacement source off) Forced operation on normal source Forced operation on replacement source Automatic operation |
| Interlocked device | MasterPact NW MasterPact NT |
| Selection modes | Circuit breaker on R Circuit breaker on N |
| Complementary function | Additional contact: transfer to replacement source only if contact is closed Voluntary transfer to replacement source (e.g. energy management commands) |
| Local signalling | Fault trip Off On |
| Test function | By opening the P25M circuit breaker supplying the controller |
| Input type | Contacts customer voluntary order to transfer to source R |
| Output type | Contacts customer: indication of operation in automatic or stop mode |
| [Ith] conventional free air thermal current | 8 A |
| [Ie] rated operational current | AC-12: 4 A AC 440 V AC-12: 5 A AC 380/415 V DC-13: 2 A 24 V |
| Standards | IEC 947-5-1 |
|---|---|
| IP degree of protection | IP20 connectors: conforming to EN 60529 IP40 front: conforming to EN 60529 IP30 side: conforming to EN 60529 |
| IK degree of protection | Front: IK07 conforming to EN 50102 |
| Product weight | 1.3 kg |