| 83.82 | |
| Multi-voltage • Mono-function • 2 pole • Transfer time can be regulated (0.05…1)s** |
|
| Contact specification | |
| Contact configuration | 2 NO (DPST-NO) |
| Rated current/Maximum peak current | 16/30 A |
| Rated voltage/ Maximum switching voltage |
250/400 V AC |
| Rated load AC1 | 4000 VA |
| Rated load AC15 (230 V AC) | 750 VA |
| Single phase motor rating (230 V AC) | 0.5 kW |
| Breaking capacity DC1: 24/110/220 V | 16/0.3/0.12 A |
| Minimum switching load | 300 (5/5) mW (V/mA) |
| Standard contact material | AgNi |
| Supply specification | |
| Nominal voltage (UN) | 24…240 V AC (50/60 Hz) 24…240 V DC |
| Rated power AC/DC | < 1.5/< 2 [VA (50 Hz)/W] |
| Operating range | 16.8…265 V AC 16.8…265 V DC |
| Technical data | |
| Specified time range | * |
| Repeatability | ± 1% |
| Recovery time | 200 ms |
| Minimum control impulse | 一 ms |
| Setting accuracy-full range | ± 5% |
| Electrical life at rated load in AC1 | 50 · 10³ cycles |
| Ambient temperature range | 一20…+60°C |
| Protection category | IP 20 |
| Ordering information | |||||
| 83. | 82. | 0. | 240. | 0000 | |
| 83: | Series | ||||
| 8: | Type 0 = Multi-function (AI, DI, GI, SW, BE, CE, DE, WD) 1 = On-delay (AI) 2 = Interval (DI) 4 = Off-delay with control signal (BE) 5 = Multi-function (AE, GE, IT, FE, EEa, DEp, BEp, SHp) 6 = Power off-delay (True off-delay) (BI) 8 = Star-delta (SD) 9 = Asymmetrical flasher (LI, LE, PI, PE) |
||||
| 2: | No. of poles 1 = 1 CO (SPDT) 2 = 2 CO (DPDT) for 83.02, 83.52 and 83.62 2 = 2 NO (DPST-NO) for 83.82 |
||||
| 0: | Supply version 0 = AC (50/60 Hz)/DC |
||||
| 240: | Supply voltage 240 = (24 … 240)V AC/DC |
||||
| 0000: | 0000 = Standard 0003 = ATEX (Ex ec nC), HazLoc and IECEx (only 83.02) |
||||