Schneider LC1D80P7 Contactor LC1D80P7C

IEC contactor, TeSys Deca, nonreversing, 80A, 60HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 230VAC 50/60Hz coil, open
SKU: RW340Y3T2308
Main
Range TeSys
Range of Product TeSys Deca
Product or Component Type Contactor
Device short name LC1D
Contactor application Resistive load
Motor control
Utilisation category AC-3
AC-3e
AC-4
AC-1
Poles description 3P
[Ue] rated operational voltage Power circuit <= 300 V DC 25…400 Hz
Power circuit <= 690 V AC
[Ie] rated operational current 125 A (at <140 °F (60 °C)) at <= 1000 V AC AC-1 for power circuit
80 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
80 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage 230 V AC 50/60 Hz
Complementary
Motor power kW 22 kW at 220…230 V AC 50 Hz (AC-3)
37 kW at 380…400 V AC 50 Hz (AC-3)
45 kW at 415…440 V AC 50 Hz (AC-3)
55 kW at 500 V AC 50 Hz (AC-3)
45 kW at 660…690 V AC 50 Hz (AC-3)
15 kW at 400 V AC 50 Hz (AC-4)
22 kW at 220…230 V AC 50/60 Hz (AC-3e)
37 kW at 380…400 V AC 50/60 Hz (AC-3e)
45 kW at 415…440 V AC 50/60 Hz (AC-3e)
55 kW at 500 V AC 50/60 Hz (AC-3e)
45 kW at 660…690 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating 7.5 hp at 120 V AC 50/60 Hz for 1 phase motors
15 hp at 230/240 V AC 50/60 Hz for 1 phase motors
30 hp at 200/208 V AC 50/60 Hz for 3 phase motors
30 hp at 230/240 V AC 50/60 Hz for 3 phase motors
60 hp at 460/480 V AC 50/60 Hz for 3 phase motors
60 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover With
[Ith] conventional free air thermal current 10 A (at 140 °F (60 °C)) for signalling circuit
125 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1100 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 640 A 104 °F (40 °C) – 10 s for power circuit
990 A 104 °F (40 °C) – 1 s for power circuit
135 A 104 °F (40 °C) – 10 min for power circuit
320 A 104 °F (40 °C) – 1 min for power circuit
100 A – 1 s for signalling circuit
120 A – 500 ms for signalling circuit
140 A – 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
200 A gG at <= 690 V coordination type 1 for power circuit
160 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 0.8 mOhm – Ith 125 A 50 Hz for power circuit
Power dissipation per pole 5.1 W AC-3
12.5 W AC-1
5.1 W AC-3e
[Ui] rated insulation voltage Power circuit 600 V CSA
Power circuit 600 V UL
Power circuit 1000 V IEC 60947-4-1
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Overvoltage category III
Pollution degree 3
[Uimp] rated impulse withstand voltage 8 kV IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 4 Mcycles
Electrical durability 0.8 Mcycles 125 A AC-1 <= 440 V
1.5 Mcycles 80 A AC-3 <= 440 V
1.5 Mcycles 80 A AC-3e <= 440 V
Control circuit type AC 50/60 Hz standard
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.85…1.1 Uc (-40…131 °F (-40…55 °C)):operational AC 60 Hz
0.3…0.6 Uc (-40…158 °F (-40…70 °C)):drop-out AC 50/60 Hz
0.8…1.1 Uc (-40…131 °F (-40…55 °C)):operational AC 50 Hz
1…1.1 Uc (131…158 °F (55…70 °C)):operational AC 50/60 Hz
Inrush power in VA 245 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))
245 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA 26 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
26 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation 6…10 W at 50/60 Hz
Operating time 20…35 ms closing
6…20 ms opening
Maximum operating rate 3600 cyc/h at 60 °C
Connections – terminals Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) – cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) – cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) – cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) – cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) – cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) – cable stiffness: solid without cable end
Power circuit: connector 1 0.006…0.08 in² (4…50 mm²) – cable stiffness: flexible without cable end
Power circuit: connector 2 0.006…0.04 in² (4…25 mm²) – cable stiffness: flexible without cable end
Power circuit: connector 1 0.006…0.08 in² (4…50 mm²) – cable stiffness: flexible with cable end
Power circuit: connector 2 0.006…0.02 in² (4…16 mm²) – cable stiffness: flexible with cable end
Power circuit: connector 1 0.006…0.08 in² (4…50 mm²) – cable stiffness: solid without cable end
Power circuit: connector 2 0.006…0.04 in² (4…25 mm²) – cable stiffness: solid without cable end
Tightening torque Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2
Power circuit 106.2 lbf.in (12 N.m) connector flat Ø 6 to Ø 8 mm
Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm)
Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25…400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support Rail
Plate
Environment
Standards EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
CSA C22.2 No 14
UL 60947-4-1
IEC 60335-2-40:Annex JJ
UL 60335-2-40:Annex JJ
IEC 60335-1:Clause 30.2
Product Certifications CCC
UL
CB Scheme
CSA
CE
UKCA
Marine
EAC
IP degree of protection IP20 front face IEC 60529
Protective treatment THIEC 60068-2-30
Climatic withstand IACS E10 exposure to damp heat
Permissible ambient air temperature around the device -40…140 °F (-40…60 °C)
140…158 °F (60…70 °C) with derating
Operating altitude 0…9842.52 ft (0…3000 m)
Fire resistance 1562 °F (850 °C) IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations contactor open 2 Gn, 5…300 Hz)
Shocks contactor open 8 Gn for 11 ms)
Vibrations contactor closed 3 Gn, 5…300 Hz)
Shocks contactor closed 10 Gn for 11 ms)
Height 5 in (127 mm)
Width 3.3 in (85 mm)
Depth 5.1 in (130 mm)
Net Weight 3.51 lb(US) (1.59 kg)
Weight 1.6 kg