| Rated surge voltage | 6 kV |
| Maximum power dissipation for nominal condition | 1.31 W |
| Number of connections per level | 2 |
| Nominal cross section | 6 mm² |
| 1 level | |
| Connection method | Push-in connection |
| Stripping length | 12 mm |
| Internal cylindrical gage | A5 |
| Connection in acc. with standard | IEC 61984 |
| Conductor cross-section rigid | 0.5 mm² … 10 mm² |
| Cross section AWG | 20 … 8 (converted acc. to IEC) |
| Conductor cross-section flexible | 0.5 mm² … 6 mm² |
| Conductor cross-section, flexible [AWG] | 20 … 10 (converted acc. to IEC) |
| Conductor cross-section flexible (ferrule without plastic sleeve) | 0.5 mm² … 6 mm² |
| Flexible conductor cross-section (ferrule with plastic sleeve) | 0.5 mm² … 6 mm² |
| Conductor cross-section flexible (2 conductors with the same cross-section, with TWIN ferrule and plastic sleeve) | 0.5 mm² … 1.5 mm² |
| 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 0.5 mm² … 1.5 mm² |
| Nominal current | 30 A |
| Maximum load current | 30 A (with 10 mm² conductor cross-section) |
| Nominal voltage | 500 V |
| Nominal cross section | 6 mm² |
| 1 level Connection cross sections directly pluggable | |
| Conductor cross-section rigid | 1 mm² … 10 mm² |
| Conductor cross-section flexible (ferrule without plastic sleeve) | 1 mm² … 6 mm² |
| Flexible conductor cross-section (ferrule with plastic sleeve) | 1 mm² … 6 mm² |
| Surge voltage test | |
| Test voltage setpoint | 4.8 kV |
| Result | Test passed |
| Short-time withstand current 4 mm² | 0.5 kA |
| 0.15 kA | |
| 1.25 kA | |
| Result | Test passed |
| Power-frequency withstand voltage | |
| Test voltage setpoint | 2.21 kV |
| Result | Test passed |