rig-well.com

Phoneix Contact QUINT-PS/1AC/24DC/10 Power supply 2866763

Primary-switched power supply unit QUINT POWER, Screw connection, DIN rail mounting, SFB Technology (Selective Fuse Breaking), input: 1-phase, output: 24 V DC / 10 A
SKU: RW757Y3T

[Input]:

AC operation
Nominal input voltage range 100 V AC … 240 V AC -15 % / +10 %
Input voltage range 85 V AC … 264 V AC
Derating IStat. Boost < 100 V AC (1 %/V)
Input voltage range DC 110 V DC … 350 V DC (typ. 90 V DC (UL 508: ≤ 300 V DC))
Electric strength, max. 300 V AC
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC
Inrush current < 15 A
Inrush current integral (I2t) < 1.5 A2s
Inrush current limitation 15 A
AC frequency range 45 Hz … 65 Hz
Frequency range DC 0 Hz
Mains buffering time > 36 ms (120 V AC)
> 36 ms (230 V AC)
Current consumption 4 A (100 V AC)
1.7 A (240 V AC)
Nominal power consumption 302 VA
Protective circuit Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi) 0.85
Typical response time < 0.15 s
Input fuse 10 A (slow-blow, internal)
Permissible backup fuse B10 B16 AC:
Permissible DC backup fuse DC: Connect a suitable fuse upstream
Recommended breaker for input protection 10 A … 20 A (Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA
DC operation
Nominal input voltage range 110 V DC … 250 V DC -10 % … +40 % (UL 508: ≤ 300 V DC)
Input voltage range 110 V DC … 350 V DC
Derating IStat. Boost < 110 V DC (1 %/V)
Current consumption 3.4 A (110 V DC)
1.5 A (250 V DC)

[Output]:

Efficiency typ. 92 % (120 V AC)
typ. 93.2 % (230 V AC)
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 18 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 10 A
POWER BOOST (IBoost) 15 A (-25 °C … 40 °C permanent, UOUT = 24 V DC )
Static Boost (IStat.Boost) 15 A
Selective Fuse Breaking (ISFB) 60 A (12 ms)
Magnetic circuit breaker tripping B2 / B4 / B6 / C2 / C4
Derating 60 °C … 70 °C (2.5 %/K)
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 35 V DC
Control deviation < 1 % (change in load, static 10 % … 90 %)
< 2 % (change in load, dynamic 10 % … 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 50 mVPP (with nominal values)
Short-circuit-proof yes
Output power 240 W
360 W
Maximum no-load power dissipation 9.1 W
Power loss nominal load max. 22 W
Rise time < 0.05 s (UOUT (10 % … 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Signal: DC OK active
Output description UOUT > 0.9 x UN: High signal
Switching voltage range 18 V DC … 24 V DC
Maximum inrush current ≤ 20 mA (short-circuit-proof)
Continuous load current ≤ 20 mA
Signal: DC OK floating
Output description Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage 30 V AC
24 V DC
Maximum inrush current 0.5 A
1 A
Continuous load current ≤ 1 A
Signal: POWER BOOST, active
Output description IOUT < IN: High signal
Switching voltage range 18 V DC … 24 V DC
Output voltage + 24 V DC
Maximum inrush current 20 mA (short-circuit-proof)
Continuous load current ≤ 20 mA
Weight 1.5 kg