rig-well.com

WAGO 750-474 Analog input 2-channel; 4 … 20 mA; Single-ended; 16 bits

● This analog input module powers field-side signal conditioners and transmits electrically isolated analog signals to the bus system.
● The 24 V field supply is derived from the module’s power jumper contacts.
● The shield directly connects to the DIN-rail.
● At approximately 25 mA, overload protection switches the measurement input to a high-resistance state. Once normal operating conditions resume, the measurement input will automatically switch back.
● This module powers 2-wire signal conditioners without dedicated power supply.
● SKU: RW2050Y1T
Number of analog inputs 2
Total number of channels (module) 2
Signal type Current
Signal type (current) 4 … 20 mADC
Sensor connection 2 x (2-wire, 3-wire)
Input filter frequency (analog) 50Hz
Input voltage (max.) 24 V
Input voltage (note) Non-linear, overload protected U = 1.2 V + 160 Ω x I meas
Signal characteristics Single-ended
Resolution [bit] 15Bit
Input resistance (max.) 220Ω
Data width 2 x 16-bit data; 2 x 8-bit control/status (optional)
Overvoltage protection 30 V, reverse polarity protected
Noise rejection at sampling frequency -100dB
Noise rejection above sampling frequency -40dB
Conversion time (typ.) 80ms
Measurement error (reference temperature) 25°C
Measurement error, deviation (max.) from the upper-range value 0.1%
Temperature error (max.) of the upper-range value 0.01%/K
Supply voltage (system) 5 VDC; via data contacts
Current consumption (5 V system supply) 75mA
Supply voltage (field) 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact)
Isolation 500 V system/field
Indicators LED (A, C) green: Function AI 1, AI 2; LED (B, D) red: Error AI 1, AI 2
Number of incoming power jumper contacts 2
Number of outgoing power jumper contacts 2
Connection technology: I/O 8 x CAGE CLAMP®
Connectable conductor materials Copper
Connection type Inputs/Outputs
Solid conductor 0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor 0.08 … 2.5 mm² / 28 … 14 AWG
Strip length 8 … 9 mm / 0.31 … 0.35 inches
Ambient temperature (operation) 0 … +55 °C
Ambient temperature (storage) -40 … +85 °C
Protection type IP20
Pollution degree 2 per IEC 61131-2
Operating altitude 0 … 2000 m / 0 … 6562 ft
Mounting position Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Relative humidity (without condensation) 95%
Vibration resistance 4g per IEC 60068-2-6
Shock resistance 15g per IEC 60068-2-27
EMC immunity to interference per EN 61000-6-2, marine applications
EMC emission of interference per EN 61000-6-4, marine applications
Exposure to pollutants Per IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 % 10ppm
Permissible SO2 contaminant concentration at a relative humidity 75 % 25ppm
Weight 0.06 kg
error:
Scroll to Top