Input:
| AC operation | |
| Nominal input voltage range | 100 V AC … 240 V AC |
| Input voltage range | 85 V AC … 264 V AC |
| Input voltage range AC | 85 V AC … 264 V AC |
| Voltage type of supply voltage | AC |
| Inrush current | < 30 A (typ.) |
| Inrush current integral (I2t) | < 0.4 A2s (typ.) |
| AC frequency range | 50 Hz … 60 Hz |
| Frequency range (fN) | 50 Hz … 60 Hz ±10 % |
| Mains buffering time | > 25 ms (120 V AC) |
| > 115 ms (230 V AC) | |
| Current consumption | typ. 0.8 A (100 V AC) |
| typ. 0.4 A (240 V AC) | |
| Nominal power consumption | 72.1 VA |
| Protective circuit | Transient surge protection; Varistor |
| Power factor (cos phi) | 0.47 |
| Typical response time | < 1 s |
| Input fuse | 2 A (slow-blow, internal) |
| Recommended breaker for input protection | 6 A … 16 A (Characteristics B, C, D, K) |
Output:
| Efficiency | typ. 87 % (120 V AC) |
| typ. 88 % (230 V AC) | |
| Output characteristic | HICCUP |
| Nominal output voltage | 24 V DC |
| Nominal output current (IN) | 1.25 A (-25 °C … 55 °C) |
| Derating | 55 °C … 70 °C (2.5 %/K) |
| Feedback voltage resistance | < 35 V DC |
| Protection against overvoltage at the output (OVP) | ≤ 35 V DC |
| Control deviation | < 1 % (change in load, static 10 % … 90 %) |
| < 2 % (Dynamic load change 10 % … 90 %, 10 Hz) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | < 60 mVPP (with nominal values) |
| Short-circuit-proof | yes |
| Output power | 30 W |
| Maximum no-load power dissipation | < 0.3 W |
| Power loss nominal load max. | < 5 W |
| Rise time | < 0.5 s (UOUT (10 % … 90 %)) |
| Response time | < 2 ms |
| Connection in parallel | yes, for redundancy and increased capacity |
| Connection in series | yes |
Mounting:
| Mounting type | DIN rail mounting |
| Assembly note | alignable: 0 mm horizontally, 30 mm vertically |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| With protective coating | no |