rig-well.com

Schneider RM35UA13MW

Voltage control relay, Harmony Control Relays, 5A, 2CO, range 15..600V, 24..240V AC DC
SKU: RWHD113U16Z
Main
Range of Product Harmony Control Relays
Relay Type Multifunction voltage control relay
Product or Component Type Voltage control relay
Relay name RM35UA
Relay monitored parameters Overvoltage or undervoltage detection
time delay Adjustable 0.3…30 s, 0 + 10 % Tt- time delay upon fault
Switching capacity in VA 1250 VA
Measurement range 15…600 V AC/DC
Contacts type and composition 2 C/O
Complementary
Reset time 1500 ms time delay
Maximum switching voltage 250 V AC/DC
Minimum switching current 10 mA 5 V DC
Maximum switching current 5 A AC/DC
operating voltage tolerance – 15 % + 10 % Un
Supply voltage limits 20.4…264 V AC/DC
Power consumption in VA 0…3.5 VA AC
Maximum power consumption in W 0.6 W DC
Control circuit frequency 40…70 Hz +/- 10 %
Immunity to microbreaks 10 ms
Resistance across terminals 150 mOhm E1-M terminals
300 mOhm E2-M terminals
600 mOhm E3-M terminals
Output contacts 2 C/O
nominal output current 5 A
Hysteresis 5…50 % threshold setting
Measurement accuracy +/- 10 % of the full scale value
Polarity Non reversible polarity on DC supply
delay at power up 600 ms
Maximum measuring cycle 30 ms measurement cycle as true rms value
Repeat accuracy +/- 0.5 % input and measurement circuit
+/- 2 % time delay
Measurement error +/- 0.05 %/°C with temperature variation
< 1 % over the whole range with voltage variation
Sensitivity scale 15…150 V E1-M terminals
30…300 V E2-M terminals
60…600 V E3-M terminals
Threshold setting 10…100 %
Quality labels CE
Insulation resistance > 500 MOhm 500 V DC between supply and relay output IEC 60255-5
> 500 MOhm 500 V DC between measurement and relay output IEC 60664-1
> 1 MOhm 500 V DC between supply and measurement IEC 60255-5
> 500 MOhm 500 V DC between supply and relay output IEC 60664-1
> 500 MOhm 500 V DC between measurement and relay output IEC 60255-5
> 1 MOhm 500 V DC between supply and measurement IEC 60664-1
Operating position Any position without derating
Local signalling LED (green) for power ON
LED (yellow) for relay ON
Overvoltage category III conforming to IEC 60664-1
[Ui] rated insulation voltage 250 V IEC 60664-1
600 V IEC 60664-1
Connections – terminals Screw terminals, 1 x 0.5…1 x 4 mm² AWG 20…AWG 11) solid without cable end
Screw terminals, 2 x 0.5…2 x 2.5 mm² AWG 20…AWG 14) solid without cable end
Screw terminals, 1 x 0.2…2 x 2.5 mm² AWG 24…AWG 12) flexible with cable end
Screw terminals, 2 x 0.2…2 x 1.5 mm² AWG 24…AWG 16) flexible with cable end
Tightening torque 5.3…8.9 lbf.in (0.6…1 N.m) IEC 60947-1
Housing material Self-extinguishing plastic
Mounting support 35 mm symmetrical DIN rail conforming to IEC 60715
Electrical durability 100000 cycles
Mechanical durability 30000000 cycles
Operating rate <= 360 operations/hour full load
Utilisation category AC-12 IEC 60947-5-1
AC-13 IEC 60947-5-1
AC-14 IEC 60947-5-1
AC-15 IEC 60947-5-1
DC-12 IEC 60947-5-1
DC-13 IEC 60947-5-1
DC-14 IEC 60947-5-1
[Un] rated nominal voltage 24…240 V AC/DC 50/60 Hz, non self-powered
Safety reliability data B10d = 290000
MTTFd = 308.2 years
Control Type Without test button
Width 1.4 in (35 mm)
Net Weight 0.18 lb(US) (0.08 kg)
Weight 0.1 kg
error: