rig-well.com

Schneider 32424 32434 trip unit STR53UE

Discontinued on 31. Mar. 2021, Without replacement
Refubished supply only
SKU: RW2000Y5T
Main
Range ComPact
Range of product NR400…630
Product or component type Trip unit
Trip unit name STR53UE F
Trip unit technology Electronic
Range compatibility ComPact NR400
ComPact NR630
Device application Distribution
Number of poles 4P
3P
Protected poles description 3t + N/2
3t
4t
Neutral position Left
Protection type for instantaneous short-circuit protection
for short time short-circuit protection
for overload protection (long time)
Trip unit rated current 250 A at 40 °C
400 A at 40 °C
630 A at 40 °C
150 A at 40 °C
[Ue] rated operational voltage <= 525 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Complementary
Long-time pick-up adjustment type Ir (thermal protection) Adjustable 48 settings
Long-time protection delay adjustment type tr Adjustable
[tr] long-time protection delay adjustment range 12…16 s at 6 x Ir
138…200 s at 1.5 x Ir
277…400 s at 1.5 x Ir
3…4 s at 6 x Ir
34…50 s at 1.5 x Ir
6…8 s at 6 x Ir
69…100 s at 1.5 x Ir
8…15 s at 1.5 x Ir
0.2…0.74 s at 7.2 x Ir
0.4…0.5 s at 6 x Ir
1…1.4 s at 7.2 x Ir
1.5…2 s at 6 x Ir
2…2.8 s at 7.2 x Ir
4…5.5 s at 7.2 x Ir
8.2…11 s at 7.2 x Ir
Short-time protection pick-up adjustment type Isd Adjustable 8 settings
[Isd] Short-time protection pick-up adjustment range 1.5…10 x Ir
Short-time protection delay adjustment type tsd Adjustable 4 settings
[tsd] Short-time protection delay adjustment range 0.015…0.06 s
0.06…0.14 s
0.14…0.23 s
0.23…0.35 s
Instantaneous protection pick-up adjustment type Ii Adjustable 8 settings
Display type Display
Environment
Standards IEC 60947-2
Product certifications LCIE
ASEFA
KEMA
ASTA
Pollution degree 3 conforming to IEC 60947
IP degree of protection IP40 conforming to IEC 60529
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -50…85 °C
Weight 0.5 kg
error: