Pepperl + Fuchs KFD2-UT2-2

Universal Temperature Converter
SKU: RWHD132U1T
Connection terminals 14+, 15- or power feed module/Power Rail
Rated voltage Ur 20 … 30 V DC
Ripple within the supply tolerance
Power dissipation ≤ 1.53 W
Power consumption max. 1.53 W
Connection side field side
Connection terminals 1, 2, 3; 4, 5, 6
RTD type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92)
type Ni100 (DIN 43760)
Measuring current approx. 200 µA with RTD
Types of measuring 2-, 3-wire connection
Lead resistance max. 50 Ω per line
Measurement loop monitoring sensor breakage, sensor short-circuit
Thermocouples type B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001)
Cold junction compensation external and internal
Measurement loop monitoring sensor breakage
Potentiometer 0 … 20 kΩ (2-wire connection), 0.8 … 20 kΩ (3-wire connection)
Voltage selectable within the range -100 … 100 mV
Input resistance ≥ 1 MΩ (-100 … 100 mV)
Connection side control side
Connection output I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-)
output II: terminal 10: source (-), sink (+), terminal 11: source (+), terminal 12: sink(-)
Output I, II Analog current output
Current range 0 … 20 mA or 4 … 20 mA
Fault signal downscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43)
Source load 0 … 550 Ω
open-circuit voltage ≤ 18 V
Sink Voltage across terminals 5 … 30 V. If the current is supplied from a source > 16.5 V,
series resistance of ≥ (V – 16.5)/0.0215 Ω is needed, where V is the source voltage.
The maximum value of the resistance is (V – 5)/0.0215 Ω.
Degree of protection IP20
Connection screw terminals
Mass approx. 130 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height 119 mm
Width 20 mm
Depth 115 mm
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Weight 0.2 kg