Specifications
Range | TeSys Deca |
---|---|
product name | TeSys GV3 |
Product or component type | Motor circuit breaker |
Device short name | GV3P |
Device application | Motor protection |
Trip unit technology | Thermal-magnetic |
Poles description | 3P |
---|---|
Network type | AC |
Utilisation category | Category A IEC 60947-2 AC-3 IEC 60947-4-1 |
Network frequency | 50/60 Hz IEC 60947-2 |
Motor power kW | 22 kW 400/415 V AC 50/60 Hz 30 kW 500 V AC 50/60 Hz 45 kW 690 V AC 50/60 Hz |
Breaking capacity | 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 12 kA Icu 500 V AC 50/60 Hz IEC 60947-2 6 kA Icu 690 V AC 50/60 Hz IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity | 100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 50 % 500 V AC 50/60 Hz IEC 60947-2 50 % 690 V AC 50/60 Hz IEC 60947-2 |
control type | Rotary handle |
[In] rated current | 50 A |
Thermal protection adjustment range | 37…50 A IEC 60947-2 |
Magnetic tripping current | 700 A |
[Ith] conventional free air thermal current | 50 A IEC 60947-2 |
[Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-2 |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV IEC 60947-2 |
Phase failure sensitivity | Yes IEC 60947-4-1 |
Suitability for isolation | Yes IEC 60947-1 |
Power dissipation per pole | 8 W |
Mechanical durability | 50000 cycles |
Electrical durability | 50000 cycles AC-3 415 V In |
Rated duty | Uninterrupted IEC 60947-4-1 |
Tightening torque | 44.3 lbf.in (5 N.m) screw clamp terminal |
Fixing mode | 35 mm symmetrical DIN rail clipped Panel screwed with 3 x M4 screws) |
Mounting position | Horizontal Vertical |
Width | 2.2 in (55 mm) |
Height | 5.2 in (132 mm) |
Depth | 5.4 in (136 mm) |
Product weight | 2.12 lb(US) (0.96 kg) |